Customization: | Available |
---|---|
Breaking Capacity: | Low Voltage Circuit Breakers |
Operation: | Electric Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Basic specification and main parameters
Frame |
63A |
Rated working voltage |
230/400V |
Rated frequency |
50/60Hz |
Rated working current |
16,25,40,63A |
Rated residual operating current |
0.03,0.1,0.3,0.5A |
Rated residual un-operating current |
0.015,0.05,0.15,0.25A |
Sensibility |
A Type,AC Type,S Type |
Maximum operating time |
In t≤0.1s , 5In t≤0.04 |
Rated making and breaking capacity |
In≤50A 500A,In=63A 630A,In=63A 1500A |
Limiting value of un-operating current |
6In |
Rated limiting short-circuit current |
10000A |
Pole number |
2,4P |
Mechanical life |
20000 |
Electric life |
4000 |
Operation principle
Each phase of conductor at the circuit breaker passes through the zero-sequence
current tr ansformer, and the secondary side of coil connects with the electromagnetic tripper.Under normal condition, the vector sum of each phase of current passing through zerosequence current transformer is zero. The flux of the zero-sequence current transformer is zero. And the secondary output voltage is zero and the circuit breaker doesn t zero,and the zero-sequence current transformer would produce the magnetic flux, and the secondary side of coil would output the voltage. Once the leak current increases to drive the output voltage at the secondary side to grow to certain level, the electromagnetic release would activate to drive the operation mechanism to act to break the contact that connects the power, finally to realize the leak protection.